Rain Master Irrigation Systems DX2 User Manual
Page 228 Chapter 10: Troubleshooting
The following schematic diagram illustrates a sample wiring
configuration of four solenoids connected to station outputs:
Controller Station Output Board
Figure 174: Output Board Station Connections
The solenoids connected to station outputs 1, 4, and 8 share one
common line return to the station output board. Station #10 is
shown as a normal operating station, which is connected
independently from the other stations (not sharing the common
connection).
When station one turns on, 24 VAC is applied to the solenoid
and the LED illuminates. If the common line is broken or open,
(as shown by the cross marks) current does not flow and the
solenoid is not energized. However, a small amount of current
flows through the solenoid coils back to each station output
LED. This causes station LEDs # 4 and #8 to illuminate,
creating the illusion that the stations are on when they are
actually inoperative.
Solenoid
STA #10
STA #8
STA #4
STA #1
Solenoid
Solenoid
Solenoid