Evolution DX2 series Manual de usuario Pagina 66

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 71
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 65
Rain Master Irrigation Systems DX2 User Manual
Page 226 Chapter 10: Troubleshooting
Monthly Flow Violation Occurred
but Program Still Operates
Consult Factory
Has the program been
set up to stop watering at water limit?
No
No
Yes
1
2
Ref. Station Setup (4-20)
To assure monthly flow violations are reported and acted
upon correctly, the upper limit checking must be enabled.
Change the limit options from Disabled to Enabled.
Yes
Ref. At Water Limit (4-13)
Change setup option from Give Warning to
Stop Watering
Has the upper limit checking of
station limits been disabled?
Start
Vista de pagina 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71

Comentarios a estos manuales

Sin comentarios