Rain Master Irrigation Systems DX2 User Manual
Page 204 Chapter 10: Troubleshooting
028 - Flow Max - Stop Water
Figure 169: Warning 028 -FM Stop Water
This warning is originated by the submaster whenever flow
violations occur. It is sent to all Flow Max participants when
any of the following conditions occur:
Unscheduled Flow
Main Line Break
Hardwire Communications Failure
Power Failures
"STA=" indicates which stations were on at the time the
command was issued. Satellites which receive this warning
terminate all irrigation.
Action:
Step 1 Read the alarms at the submaster to determine the
reason for the alarm.
Step 2 Read the alarms at the satellites(s) for satellite
specific information.
Step 3 IMPORTANT:
Upon resolution of problem, CLEAR all warnings at
all satellites.
WARNING = FM STOP WATER 06/14/96 10:45PM
STA= PUMP, N.O., MV1, |¾||½|