Rain Master Irrigation Systems DX2 User Manual
Page 256 Appendix B: Current Monitor
Auto Limits Procedure
The Auto Limits feature establishes upper and lower limits of
current by automatically measuring each station. Upper and
lower percentages of the measured values are calculated to
establish the limits for each station.
The current upper default percentage is set at 20% above the
measured value; a .50 Amps measurement percentage value for
the upper limit would therefore be .60 Amps. The lower default
percentage is set at 50% below the measured value; a .50 Amps
measurement percentage value for the lower limit would
therefore be .25 Amps.
The default values may be changed at any time using the
F2=SET LIMIT(%) option. The percentage value ranges are
given on the percentage entry display screen.
Note: If the default values are not suitable for your
application, the SET LIMITS percentages must be
entered prior to running the Auto Limits. Select
F2=SET LIMIT and set your percentages
accordingly.
Step 1 Advance to the Auto Limits Option display through
the following sequence:
Figure 185: Auto Limits
Step 2 Select F1=RUN AUTO LIMITS and verify the
following three option menu:
|F1|=RUN AUTO LIMITS |F2|=SET LIMIT
%
|½|
F1=Main Menu
F5=Setup
F3=Stations
F3=Auto Limits